IOLM 8-EIP Connecting the Power

The following provides an installation and configuration overview for the IOLM 8-EIP. IOLM 8-EIP

[Note]
Note

Important!

To avoid possible damage, ensure that the power supply used with the IOLM 8-EIP is powered off before connecting power cables.

IOLM 8-EIP provides dual M12 (T-coded) power connectors.

PinInput - MaleOutput - FemaleComtrol Power Cable

1

+24VDC (US)

+24VDC (US)

Brown

2

GND UA

GND UA

White

3

GND US

GND US

Blue

4

+24VDC (UA)

+24VDC (UA)

Black

5

Not connected

Not connected

Not applicable

If you purchased cables from Pepperl+Fuchs Comtrol, Inc., you can refer to web site for cabling information.

The following table contains power-related information about the power supply.

[Note]
Note

Power connectors must have an approved cable or protective cover attached to the port guarantee IP67 compliance.

Power Supply Voltage/CurrentValues

Power Supply In

Vs

Va

Maximum

10A

10A

Port 1 IO-Link Connector

C/Q (Pin 4)

Vs (Pins 1 and 3)

Maximum

200 mA

1.6A

Ports 2-8 IO-Link Connector

C/Q (Pin 4)

Vs (Pins 1 and 3)

Maximum

200 mA

500 mA

IO-Link Master Power

100mA @ 24VDC (Vs)

Power Supply Out

Vs

Va

Maximum

10A†

10A††

[Note]
Note

† Vs output available is determined by subtracting the following from the available input current.

  • IO-Link Mode module power

  • Actual C/Q current for each IO-Link Master port

  • Actual Vs current for each IO-Link port

†† VA output available is the same as the available Va input current

You can use this procedure to connect the IOLM 8-EIP to a power supply.

  1. Securely attach the power cable between the male power connector and the power supply.

  2. Either attach a power cable between the female power connector and another device to which you want to provide power or securely attach a connector cap to prevent dust or liquids from getting into the connector.

    • PWR - The LED is lit indicating that the IO-Link Master is receiving power.

    • MS - The MS LED is off, which means that the IOLM is operating as expected.

      [Note]
      Note

      If the IOLM 8-EIP has U-Boot bootloader v1.25 or higher, the MS LED is lit during the power-on cycle.

    • NS - if the NS LED is off; that means that there is no PLC connected. If the NS LED is lit and green, that means that a PLC is connected.

      [Note]
      Note

      If the IOLM 8-EIP has U-Boot bootloader v1.25 or higher, the NS LED is lit during the power-on cycle.

    • The Link LEDs should be steady green indicating that the link is up. The ACT LED flashes to indicate network activity.

See the Troubleshooting page for addition information about the IOLM 8-EIP LEDs.